EasyManuals Logo

Siemens FDA2 Series User Manual

Siemens FDA2 Series
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #27 background imageLoading...
Page #27 background image
4.1 Site survey
Survey the site where the aspirating smoke system is to be installed in order to
obtain key information for planning the pipe system.
Condition (material and surface) of:
Walls
Floors
Ceilings
Furniture
Decoration
Type of rooms in the fire section
Type of heating
Underfloor heating
Ceiling heating
Radiant heaters
Air conditioning system
Cavities
False floor
False ceiling
Ducts
Shafts
Room geometry in the fire zone
Demarcation of the fire zone
Availability of up-to-date construction plans
Dust load in the environment to be monitored
4.2 Calculating the pipe system
The data acquired on site provides the basis for calculating the pipe system using
the software 'FXS2056 ASD Asyst‑Tool V3'.
The software 'FXS2056 ASD Asyst‑Tool V3' must be used to perform the
calculation prior to every installation.
Planning
Site survey
4
A6V11783979_en--_a 27 | 48

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens FDA2 Series and is the answer not in the manual?

Siemens FDA2 Series Specifications

General IconGeneral
BrandSiemens
ModelFDA2 Series
CategorySmoke Alarm
LanguageEnglish

Related product manuals