Parameter set DIP switch
No. Name Alarm for n%
attenuation
1 2 3 4 5 6
04 Sensitive with British
Standard Alarm
50%
OFF
OFF
ON
OFF
OFF
OFF
05 Very sensitive with
open line
30%
ON
OFF
ON
OFF
OFF
OFF
06 Very sensitive with
British Standard Alarm
40%
OFF
ON
ON
OFF
OFF
OFF
Table 1: Set parameter set
Parameter set2 meets the requirements of standard EN54‑12.