4.7 Preliminary setting of the detector optics (optional)
Preliminary setting of the detector optics must only undertaken when the signal
level was below 100 and/or the distance indication was incorrect.
w The detector line is switched on.
w The adjustment device is connected to the detector and must be set to 'Adjust'.
w The signal level is below 100 and/or the distance indication does not match the
detection distance.
1.
Mount the sighting system on the detector. The mirror(1) and the front sight(2)
must be free from clearance.
2.
Ensure that the two safety screws(5) are loosened.
3.
Use the knurled screws to align the detector optics with the reflector (3):
Knurled screw(6) for vertical adjustment
Knurled screw(4) for horizontal adjustment
The reflector (3) and the front sight(2) must be on the axis of the circular
mark on the mirror.
4.
Simultaneously check the signal level and the distance indication on the
adjustment device.
a Following successful alignment of the detector optics, the signal level must
be over 100 and the distance indication match the detection distance with
an accuracy of 10%.
5.
Remove the sighting system.
1 2
3
4
5
6
5
Figure 23: Preliminary setting
1 Mirror 4 Knurled screw for horizontal
adjustment
2 Notch 5 Safety screws
3 Reflector 6 Knurled screw for vertical
adjustment