4 Commissioning
Sequence
1. Set parameter set
2. Install detector unit
3. Install detector heating unit (optional)
4. Insert filter in detector (optional)
5. Commissioning the adjustment device
6. Checking the signal level and distance
7. Preliminary setting of the detector optics (optional)
8. Fine-tuning of the detector optics
9. Initializing the detector
10. Testing detectors
The types are described in the following chapters.
4.1 Set parameter set
Setting the parameter set depends on the detector line.
FDnet/C-NET detector line
The parameter set is set using control panel.
The procedure for setting the parameter set via the control panel is described in
the control panel documentation.
Collective detector line
The parameters are set with the DIP switches in the detector unit.
l Use DIP switches (1) to set the required parameter set (see table below).
1
Figure 17: Detector unit with DIP switches
Parameter set DIP switch
No. Name Alarm for n%
attenuation
1 2 3 4 5 6
01 Standard with open
line
65%
ON
OFF
OFF
OFF
OFF
OFF
02 Standard with British
Standard Alarm
65%
OFF
ON
OFF
OFF
OFF
OFF
03 Sensitive with open
line
50%
ON
ON
OFF
OFF
OFF
OFF
Commissioning
Set parameter set
4
A6V10332811_e_en_-- 21 | 44