Indication location Example Meaning
Top left 555 Signal level before initialization
The signal level must be between 255 and 1195 for initialization.
Otherwise initialization is not possible.
100% Standardized signal value as % of the current compensation value
During initialization, the signal level is equalized to the compensation
value 100%.
Bottom left 50m Distance in meters between detector and reflector
Top right Adjust Detector not yet initialized
Bottom right OK Last initialization successfully completed
Indication before initialization:
Indication after initialization:
Commissioning
Commissioning the adjustment device
4