4.
Activate the initialization procedure by pressing the button(3). The detection
distance must not be interrupted during initialization!
a During initialization, the following is displayed on the adjustment device:
Initialization
....................
a Following successful initialization, 100%±3% and the effective detection
distance is displayed on the adjustment device. Example:
5.
Copy the standardized signal value onto the two labels.
50 1133 100
FDL241-9; commissioning & adjustment data
(values displayed on adjustment device)
distance
[m]
deviate-
signal
[%]
covered-
reflector
value
[%]
values
date &
action
signal-
value
[-]
100%
50m
OK
a The detector is initialized.
Troubleshooting during initialization
● If the standardized signal value is not within 100%±3% or if the detection
indication displayed deviates by more than 10% from the effective detection
distance, repeat the initialization process from step 4.
● If initialization fails, the following is displayed:
Remedy the error and repeat the initialization process. Possible causes for
failed initialization:
Signal Possible cause
Not stable Moving obstacle
Too high Strong reflection
Too low ● Detection distance too large
● Reflector too small
● Reflector aligned incorrectly
● Reflector covered
Commissioning
Initializing the detector
4
A6V10332811_e_en_-- 33 | 44