Reset voltage DC2…4V
Reset time at reset voltage DC2V 1…2s
Protocol Collective (with and without current
limitation)
Compatibility See 'List of compatibility'
Addressed detector line and collective detector line
External alarm indicators
Number of external alarm indicators that
can be connected
2
Voltage DC6…17V
Current 9…15mA
Length of line Max. 30m with unshielded cables
(recommended) or if the shielding on
the detector is connected to the
positive pole for the external alarm
indicator
Max. 5m, if the shielding is
connected to earth
Flashing interval times on FDnet/C-NET
detector line:
● Bright 15ms
● Dark 1s
Flashing interval times on collective
detector line
Control panel-specific
Device characteristics
Infrared transmitter:
● Wavelength 950nm
● Pulse frequency 4Hz
Compensation (if the ray attenuates)
Compensation speed
2.3%/h
Alarm integration 6…16s
Detection distance:
● Without filter 10…100m
● With short distance filter DLF1191‑AA 8…12m
1
● With short distance filter DLF1191‑AB 5…10m
1
● Maximum angle misalignment 0.4°
1
The detection distance of 10…100m meets the requirements of standard EN54‑12.
Detector heating unit
DLH1191A
Operating voltage DC20…30V
Operating current 30…50mA
Resistance 600Ω
Heating unit in reflector
for long distance (prism)
DLR1191
Operating voltage DC20…30V
Operating current 30…50mA
Resistance 600Ω
Specifications
Technical data
5
36 | 44 A6V10332811_e_en_--