Commissioning
Restart the station
7
58 | 62
Building Technologies
A6V10211094_f_en_
--
Fire Safety
2015
-
-
15
PMI & mainboard FCM2004 and FCM2027
ϖ Switches S38-1 and S38-2 are set to the 'OFF' position on the PMI &
mainboard FCM2004.
κ On the PCB of the operating unit, press and hold down the 'S32' button for
<2 s.
The 'Station' shuts down.
The 'Station' is switched off for several seconds.
The 'Station' restarts.
CPU card
1. Briefly press the 'S8' button on the CPU card until a 'R' is displayed on the LED
matrix display.
2. As soon as the 'R' is displayed, press and hold the 'S8' button for approx. 2 s to
confirm the selection.
A checkmark on the LED matrix display confirms the selection.
The CPU card is restarted.
You will find information on the
CPU card FCC2004, the LED matrix display,
and operating the 'S8' button in document A6V10210368. See chapter 'Applicable
documents'.