LME Series
Technical Instructions
LME-1000
SCC Inc. Page 9 Section 3
LME73 Phase Diagrams
T
he Siemens LME7 burner controls can perform a number of different burner sequences based
upon which PME7 program module is used, how certain parameters are set, and how the LME7
is wired.
Each program module has an associated phase diagram. The phase diagrams illustrate when
input and output terminals are expected to be energized or de-energized. A legend on the
bottom of each page describes the various symbols used in the diagrams.
Notes:
1) A jumper can be added between terminals X7-04.4 and X7-01.3 for direct spark ignition.
If this jumper is added, pilot valve output X7-01.3 and main valve output X7-04.4 will be
energized from phase 40 through the end of operation.
2) On PME73.811A1, if the LME7 is set to perform valve proving, valve proving will always
take place during shutdown unless it is the next startup following a lockout or power loss,
or if the postpurge time (parameter 234) is set to 0. In that case, valve proving occurs
during startup and shutdown. When valve proving occurs during shutdown, it will happen
at the same time as postpurge. Phases 80-83 will be displayed on the LME7 and the AZL23
even though postpurge (phase 74) is also occurring at the same time. The actual
postpurge time will be at least the sum of all four valve proving time parameters (242,
243, 244, and 245). When valve proving occurs during startup, it will happen at the same
time as prepurge. Phases 80-83 will be displayed on the LME7 and the AZL23 even
though prepurge (phase 30) is also occurring at the same time. The actual prepurge time
will be at least the sum of all four valve proving time parameters (242, 243, 244, and 245).
3) On PME73.840A1, if the LME7 is set to perform valve proving on startup, valve proving
takes place at the same time as prepurge. Phases 80-83 will be displayed on the LME7
and the AZL23 even though prepurge (phase 30) is also occurring at the same time. The
actual prepurge time will be at least the sum of all four valve proving time parameters
(242, 243, 244, and 245).
4) On PME73.840A1, if the LME7 is set to perform valve proving on shutdown, valve proving
takes place at the same time as postpurge. Phases 80-83 will be displayed on the LME7
and the AZL23 even though postpurge (phase 74) is also occurring at the same time. The
actual postpurge time will be at least the sum of all four valve proving time parameters
(242, 243, 244, and 245).

Table of Contents

Other manuals for Siemens LME7 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens LME7 Series and is the answer not in the manual?

Siemens LME7 Series Specifications

General IconGeneral
BrandSiemens
ModelLME7 Series
CategoryController
LanguageEnglish

Related product manuals