BACnet MS/TP Connection Details
BACnet MS/TP protocol selection and addressing is done using the PC tool OCI417
Configuration Utility (see next section).
Supported addresses: 0-127
Supported baud rates: 9600, 19200, 38400, 57600, 76800 and 115200
Supported data bits: 8
Supported parity and stop bits: none (1 stop bit)
Supported device instances: 0-4194302