130/245 
Building Technologies Division  Basic Documentation LME7...   CC1P7105en 
Infrastructure & Cities Sector  18 PME73.831…  29.11.2011 
 
18 PME73.831… 
18.1 Program sequence PME73.831… 
 For connection diagram fuel trains G/Gp1/Gp2 (without valve proving) 
710 5d 60e/ 1111
M
Z
V1
V2
AL
K1X2-02 Pin 3
Actuator position
High-fire
Ignition load
Low-fire
CLOSE
R
LR-OPEN
LR-CLOSE
LP
Pmin
P LT
ION / QRA
QRB / QRC
X3-04 Pin 5
Relay
contact
Function / inputs
Display and operating unit parameter number
LED permanent
LED flashing
tw      t11 t10           t12    t3    t3n      t4                   t8       td4   td1  td3   td2
Standby       Startup       Operation    Shutdown    Valve proving
If parameter
                                    P241 =1 (ON)
Can be
parameterized
t1        
TSA
259        225    260 226 257     230 231  260 232  234
Relay
contact
Function / outputs
SK
X3-04 Pin 1
X5-03 Pin 1
X5-03 Pin 3
X65 Pin 1
X5-03 Pin 2
X65 Pin 1
X3-02 Pin 1
X5-01 Pin 2
X2-02 Pin 4
X9-04 Pin 2
PV
SV
K1X6-03 Pin 3
K4X2-01 Pin 3
K5X4-02 Pin 3
K2/2X7-01 Pin 3
K7X7-04 Pin 4
X7-02 Pin 3
K2/1X2-03 Pin 3
Phase number
21 22 24 22 30  30 36 38 40 42 44 50 54 54  72 74 10  80 81 82 83 
oP1
t9             t12          t5             
SA-NL
K11X2-09 Pin 3
SA-KL
K12X2-09 Pin 2
SA-ZU
X2-09 Pin 1
SA-R
X2-09 Pin 4
Output SA-ZL cams
K2/2X2-09 Pin 7
Input SA-ZL cams
X2-09 Pin 8
X2-02 Pin 4
*3
*1 *2
*3
*4
*1
*2
 
Fig. 63: Program sequence PME73.831... to connection diagram fuel trains (G)/(Gp1)/(Gp2) 
 
 
Version 1: 
  Ignition load < low-fire 
 Prepurging in high-fire 
  Parameter 515 = 1 (requirement parameter 259.01 > 0 seconds)