21.5  Multistage/modulating mode via 3-position 
step input X5-03 
The signal time of a control pulse is a minimum of 147 ms. 
 
21.5.1 Maximum possible resolution 
 
The maximum possible resolution via 3-position step input X5-03 is calculated 
according to the following formula: 
 
Working range in angular degrees x 0.147 s 
---------------------------------------------------- = maximum possible resolution in angular degree 
          Running time in seconds 
 
Example:
 Actuator, 30 seconds running time for 90° 
 
90° x 0.147 s 
------------------- = 0.441° ≈ 0.5° 
      30 s 
 
21.6  Modulating mode via analog input signal 
X65 
 
21.6.1 Maximum possible resolution 
 
The maximum possible resolution of analog input signal X65 is determined via the 
connected ASZxx.3x feedback potentiometer. 
For actuators having a working range of 0...90°, the resolution is about 0.5°. 
For actuators having a working range of 0...135°, the resolution is about 0.8°. 
 
21.6.2 Standardization of modulation range 
 
In the modulation range, the analog input signal is standardized. This means that the 
low-fire position corresponds to a preset output of 0% = 0 V-/0 mA-/4 mA-/0  input 
signal and the high-fire position corresponds to a preset output of 100% = 10 V-/ 
20 mA-/135  input signal. 
 
The modulation range in angular degrees corresponds to the angular rotation from the 
low-fire to the high-fire position. 
 
Calculation: High-fire position minus low-fire position = modulation range.