89/245 
Building Technologies Division  Basic Documentation LME7...   CC1P7105en 
Infrastructure & Cities Sector  14 PME72.541...  29.11.2011 
14.5 Time table and settings for program sequence PME72.541...  
 
Type  Times in seconds 
PME72.541... 
tw 
TSA 
max. 
t1 
min. 
t3 
min. 
t3n 
approx. 
t4 
min. 
t5 
min. 
t8 
min. 
t9 
approx. 
t10 
approx. 
t11 
approx. 
t12 
approx. 
t22 1) 2)  3) 
Requirement  2.5 3 30 6  2.5  9 8.5 15  3  15  300  300 t9+1 --- --- --- 
Factory setting  --- --- --- ---  ---  --- --- ---  ---  ---  ---  ---  --- --- --- --- 
Max. 2.5 3 --- --- --- --- --- --- --- --- --- --- --- 1 0.45 0.45 
Min.  ---  ---  30  6  ---  9 8.5 15  ---  ---  ---  ---  --- 0.3 0.3 --- 
Step size  --- --- --- ---  ---  --- --- ---  ---  ---  ---  ---  --- --- --- --- 
 
Legend 
 
tw  Waiting time  t8  Postpurge time 
TSA  Safety time  t9  Interval: Fuel valve 1 ON - pilot valve OFF 
t1  Prepurge time  t10  Specified time air pressure switch state message (timeout) 
t3 Preignition time  t11 
Opening time of actuator (timeout) 
t3n Postignition time  t12 
Closing time of actuator (timeout) 
t4  Interval: End of safety time - fuel valve 1 ON  t22  2nd safety time  
t5  Interval: Pilot valve OFF - load controller release     
 
1)  Response time to a change of signal by the air pressure switch (opens) and response time in the event of loss of flame 
2)  Response time to a change of signal by the inputs
 (e.g. pressure switch-min) 
3)  Flame detection time