21/245 
Building Technologies Division  Basic Documentation LME7...  CC1P7105en 
Infrastructure & Cities Sector  2 System makeup/function description  29.11.2011 
 
2 System makeup/function description 
 
The LME7... is a microprocessor-based burner control with matching system 
components for the control and supervision of forced draft burners of medium to high 
capacity. 
 
LME7… are used for the startup and supervision of 1- or 2-stage forced draft burners in 
intermittent operation. The flame is supervised with an ionization probe, optionally with 
flame detector QRA2..., QRA4.U or QRA10.... 
-  Gas burner controls to EN 298 : 2003 
-  Oil burner controls to EN 230 : 2005 
-  For forced draft gas burners to EN 676 
-  For forced draft oil burners to EN 267 
 
Integrated in the LME7... basic unit are: 
 Burner control 
 BCI for connection a display or PC 
  Only LME72.../LME73...: Control for one actuator 
  Lockout reset button (info button) 
  3 multicolor signal lamp LED for operations and fault notifications 
  Optional: Analog inputs for load controller DC 0...10 V, DC 0/4...20 mA, 0...135 Ω 
  3 x 7-segment display for service, fault and operating state information 
  Interface for program module 
 
 
Figure 2: Example: Modulating gas burner