209/245 
Building Technologies Division  Basic Documentation LME7...  CC1P7105en 
Infrastructure & Cities Sector  25 Operation via internal LED  29.11.2011 
 
25.4.5  Display of preset output 
 
 
Note: 
Display is possible only when … 
  in operating mode or standby, 
  program sequence for modulating operation via analog preset output. 
 
A
 
LCD Bild 13/0908
 
 
Press 
A
 for display of the relative current position of the 
actuator. 
Signal lamp blinks green. 
 
Display shows .oP. 
 
Press 
A
 (1…3 seconds) for display of the relative current 
position. 
Signal lamp blinks green. 
The relative value .57 of the current position is displayed. 
 
PME7... with actuator 
control: 
Position of actuator 0° 
0  value of potentiometer = 
0% display 
 
Position of actuator high-fire 
>0° 
<90° = value of 
potentiometer 
<1000  = 100% display 
>0  <1000  
 
PME7... with PWM fan: 
 
Current speed 
0 rpm = 0% display 
 
Current speed corresponds 
to the rated load speed = 
100% display 
A
 
1...3 s 
 
 
Example: Value .57 
 
A
 
>3 s 
 
 
When pressing 
+
 for >3 seconds, the point after the 
number begins to blink. 
When the button is released, the value is displayed for 2 
minutes. 
Signal lamp blinks green. 
Then, the normal display appears. 
 
Display: Value 57, point . blinks.