199/245 
Building Technologies Division  Basic Documentation LME7...  CC1P7105en 
Infrastructure & Cities Sector  24 Error code list with operation via external AZL2... display  29.11.2011 
 
24  Error code list with operation via 
external AZL2... display 
 
Note: 
Display depends on program! 
 
Error code  Clear text  Possible cause 
bAC Er3 
Fault of compatibility program module to basic 
unit during backup process 
Program sequence of program module does not 
match the basic unit 
     
Err PrC  Fault of program module 
- Error in data content of program module 
- No program module fitted 
     
Loc: 2 
No establishment of flame at the end of safety 
time  
- Faulty or soiled fuel valves 
- Faulty or soiled flame detector 
- Poor adjustment of burner, no fuel 
- Faulty ignition equipment 
Loc: 3 
Air pressure faulty (air pressure switch welded 
in no-load position, decrease to specified time 
(air pressure switch response time) 
Air pressure switch faulty 
- Loss of air pressure signal after specified time 
- Air pressure switch has welded in no-load position 
Loc: 4  Extraneous light  Extraneous light during burner startup 
Loc: 5 
Air pressure faulty, air pressure switch welded 
in working position 
Timeout air pressure switch 
- Air pressure switch has welded in working position 
Loc: 6  Fault of actuator 
- Actuator faulty or blocked 
- Faulty connection 
- Wrong adjustment 
Loc: 7 
Loss of flame 
Too many losses of flame during operation  
(limitation of repetitions) 
- Faulty or soiled fuel valves 
- Faulty or soiled flame detector 
- Poor adjustment of burner 
Loc: 8  ---  Free 
Loc: 9  ---  Free 
Loc: 10 
Error not relatable (application), internal error  Wiring error or internal error, output contacts, other 
faults 
Loc: 12  Valve proving  Fuel valve 1 leaking 
Loc: 13  Valve proving  Fuel valve 2 leaking 
Loc: 14  POC error  Error valve closure control POC 
Loc: 20  Gas pressure switch-min open  Gas shortage 
Loc: 22  Safety loop open 
- Gas pressure switch-max open 
- Safety limit thermostat cut out 
Loc: 60 
Analog power source 4...20 mA, I <4 mA 
Wire breakage 
Loc: 83  PWM fan faulty 
- PWM fan does not reach the target speed within  
  the preset period of time, or 
- After reaching the target speed, the PWM fan  
  leaves the tolerance band again (P650) for a time  
  exceeding the tolerance time speed deviation  
  (P660) 
Loc: 138  Restore process successful  Restore process successful 
Loc: 139  No program module detected  No program module plugged in 
Loc: 167  Manual locking  Manual locking 
Loc: 206  AZL2... incompatible  Use the latest version 
Loc: 225  PWM fan faulty  - Fan speed dropped below the minimum prepurge