213/245 
Building Technologies Division  Basic Documentation LME7...  CC1P7105en 
Infrastructure & Cities Sector  25 Operation via internal LED  29.11.2011 
 
25.6  First startup with a new program module or 
in case of replacement of program module 
 
 
 
Alternately 
 
 
 
 
Display shows alternately rSt and PrC. 
 
Display shows the replacement of the program module. 
 
Signal lamp blinks red once and yellow twice alternately. 
 
Press 
nfo
 for >3 seconds to start data download from the 
program module. 
Signal lamp blinks yellow. 
The process of 3 seconds is supported by a short flash of 
the yellow signal lamp. 
 
nfo
 
>3 s 
 
 
Note: 
If you press 
nfo
 for <3 seconds, data download does not 
start. To start the restore process again, the LME7... must 
be reset by switching mains ON/OFF. 
 
 
 
 
Display shows run during download (restore process) of the 
program sequence. 
 
 
 
Alternately 
 
 
Display shows alternately End and rSt. 
 
Display shows the end of data exchange. 
 
Signal lamp blinks red. 
 
 
After 2 minutes, the unit changes to Loc 138 
 
 
 
 
LCD Bild 06/0908
 
Alternately 
 
 
After the restore process, the unit is automatically in 
the lockout position (LOC 138) and must be reset for 
operation!