Parameter 
number 
Parameter  Edit  Value range  Resolution  Factory setting  Password level 
reading from 
level 
Password level 
writing from level 
259.00  Opening time of actuator (timeout)  Edit  0 s  1237 s  4.851 s  67.914 s  SO  OEM 
259.01  Opening time of actuator from ignition load to low-fire position  Edit  0 s  37.485 s  0.147 s  14.994 s  SO  OEM 
259.02  Opening time of actuator from low-fire to ignition load position  Edit  0 s  37.485 s  0.147 s  14.994 s  SO  OEM 
260  Closing time of actuator (timeout)  Edit  0 s  1237 s  4.851 s  67.914 s  SO  OEM 
              
515 
Actuator position during prepurge time and postpurge time 
0: Purging in low-fire 
1: Purging in high-fire 
Edit  0  1  1  1  SO  OEM 
560  Pneumatic combustion control 
0 = off/3-step modulation 
1 = PWM fan/analog modulation 
2 = air damper/analog modulation  
      (feedback potentiometer ASZxx.3x required) 
Edit  0  2  1  0  SO  SO 
              
600  Power setting               
654  Analog input (feedback potentiometer ASZxx.3x required) 
0 = 3-position step input 
1 = 0...10 V 
2 = 0...135  
3 = 0...20 mA 
4 = 4...20 mA with lockout at I <4 mA 
5 = 4...20 mA 
Edit  0  5  1  0  SO  SO