Siemens Building Technologies Basic Documentation LMU54... / LMU64... CC1P7494en
HVAC Products 7 DHW control (BWR) 07.11.2002
Instantaneous DHW heating system with plate heat exchanger (system 07)
The plate heat exchanger is constantly maintained at the DHW comfort temperature
Using comfort sensor B3, DHW demand is detected via dT supervision
Outlet temperature control is accomplished with sensor B7
DHW demand is detected via dT supervision with sensor B3. Temperature control is
accomplished directly with sensor B7.
With sensor B3 via dT supervision (parameter «dTzapfHz» in heating mode or
standby; parameter «dTzapfKomf» in comfort mode)
Control sensor: Directly with return sensor B7 via PID control
Boiler output: Modulating between minimum and maximum
Setpoint: T_set_DHW, depending on the DHW compensation
variant (e.g. potentiometer, HMI, QAA73..., etc.)
Differentials: «SdBwAus1», «SdBwEin1»
With sensor B3 via dT supervision (parameter «dTzapfEnde»)
Q1 / diverting valve are always in operation ( DHW circuit)
The plate heat exchanger is constantly maintained at the DHW comfort temperature
using comfort sensor B3.
When the DHW comfort temperature is not reached
Control sensor: With comfort sensor B3
Boiler output: Minimum (fixed value)
Setpoint: Parameter «TbwBereit» (if «KonfigRg2.1 = 1»)
Differentials: SdBwEin2, SdBwAus2Max
When the DHW comfort temperature is reached.
During comfort control:
Q1 / diverting valve are always in operation ( DHW circuit)
After comfort control:
Relevant outputs are activated in the DHW / heating circuit ( è KonfigRg2.0)
If «B2 > TqNach»: As long as «B2 < TqNach»
or
If «B2 < TqNach»: For the fixed time of one minute
To compensate a possible temperature offset, a setpoint readjustment for comfort and
outlet temperature control mode can be implemented:
Parameters «dTbwKomfxx» for a setpoint of 40 °C / 60 °C in comfort mode
Parameters «dTbwAuslxx» for a setpoint of 40 °C / 60 °C in outlet temperature
control mode
In addition - as an option - an external DHW flow switch can be used to generate a
demand (parameter «KonfigRg8»)
Aqua-booster system
Hydraulic diagram
Operating mode
Outlet temperature control
DHW demand
Control
End of demand
Pump / diverting valve
overrun
Comfort control
DHW demand
Control
End of demand
Pump / diverting valve
overrun
Miscellaneous