127/171
Siemens Building Technologies Basic Documentation LMU54... / LMU64... CC1P7494en
HVAC Products 10 Technical data 07.11.2002
10.2 Clip-in
10.2.1 AGU2.500...
Mixing circuit pump and mixing valve
- Voltage AC 230 V +10 % -15 %
- Current 5 mA ... 1 A, cos ϕ > 0.8
When assigning loads to the outputs, the total current draw of the LMU… system must
be taken into consideration!
Flow sensor NTC 10 kΩ like boiler sensor
10.2.2 AGU2.51x
Up to 3 outputs (K1...K3)
When using 2 clip-in modules with the LMU…, only 2 outputs possible
- Voltage AC 230 V +10 % -15 %
- Current 5 mA ... 1 A, cos ϕ > 0.8
When assigning loads to outputs K1...K3, the total current draw of the LMU… system
must be taken into consideration!
Version Input Remarks
AGU2.511A109 0...10 V Note polarity
AGU2.513A109 (0)4...20 mA Note polarity
AGU2.514A109 NTC 10 kΩ Like boiler sensor
AGU2.515A109
1)
1) Contact rating: Nom. DC 34 V / 5 mA
The inputs may only be used with safety extra low-voltage (SELV) and may not be
connected to protective earth (PE)!
Outputs
Electrical connections
Note
Input
Outputs
Electrical connections
Note
Input
Note