Siemens Building Technologies Basic Documentation LMU54... / LMU64... CC1P7494en
HVAC Products 1 Overview 07.11.2002
1.2 Features
Below, the full functionality of the LMU... is described. For information on the scope of
functions of a specific unit, refer to the relevant version / configuration.
Gas burner control conforming to EN 298 for intermittent operation
Integrated boiler / burner control for space heating and DHW operation
Sequence control depending on the boiler’s capacity: < 70 kW, 70 - 120 kW, or > 120 kW.
Boiler capacities up to about 600 kW can be handled (depending on the type of fan /
gas valve used)
Integrated electronic (safety) limit thermostat
Integrated limit thermostat function
Direct ignition of the main flame by means of
integrated single-pole high-voltage ignition (with the choice of single-electrode
operation)
external AC 230 V ignition control (optional)
Continuous (analog) ionization current supervision with optional indication of flame
intensity
Gas valve control AC 230 V (RAC optional)
Number of start repetitions can be programmed
Quick startup (especially in connection with instantaneous DHW systems)
Fan supervision
Optimization of combustion (optional)
Control of an AC 230 V fan (DC 24 V fan optional)
Ignition load precontrol via speed readjustment
Adaptive postpurge level of fan speed
Load limitation (fan limitation by minimum / maximum speed and / or flame signal)
Number of fan feedback pulses can be selected
Flame stabilization time
Boiler cycling protection via minimum boiler off time
Dynamic switch-off differentials for space heating (Hz) and DHW (Bw) operation
Pump and diverting valve kick
Frost protection functions for the plant, the boiler, DHW and the room
Water pressure supervision (pressure sensor with static and / or dynamic supervision,
contact for pressure switch, flow switch)
Flue gas temperature supervision
OCI420 clip-in for communication, LPB interface for ALBATROS system world
AGU2.500 clip-in for additional heating circuit
AGU2.51x clip-in function module
- inputs: NTC, 10 k
digital input
0(4)...20 mA
DC 0...10 V
- outputs: max. 3 relays AC 230 V
Safety functions
Supervision / protective
functions for the plant
Auxiliary modules
(clip-in)