141/171
Siemens Building Technologies Basic Documentation LMU54... / LMU64... CC1P7494en
HVAC Products 12 Parameter list / legend of parameter bit fields LMU... 07.11.2002
12.2 Lockout position storage
No
QAA73...
AGU2.310
Name Function Level
QAA73...
AGU2.310
700 Stoer1 1st past value of lockout code counter Engineer *
701 StrPn1 1st past value of lockout phase Engineer *
702 StrDia1 1st past value of internal diagnostic code Engineer *
703 Stoer2 2nd past value of lockout code counter Engineer *
704 StrPn2 2nd past value of lockout phase Engineer *
705 StrDia2 2nd past value of internal diagnostic code Engineer *
706 Stoer3 3rd past value of lockout code counter Engineer *
707 StrPn3 3rd past value of lockout phase Engineer *
708 StrDia3 3rd past value of internal diagnostic code Engineer *
709 Stoer4 4th past value of lockout code counter Engineer *
710 StrPn4 4th past value of lockout phase Engineer *
711 StrDia4 4th past value of internal diagnostic code Engineer *
712 Stoer5 5th past value of lockout code counter Engineer *
713 StrPn5 5th past value of lockout phase Engineer *
714 StrDia5 5th past value of internal diagnostic code Engineer *
715 Stoer_akt Current value of lockout code counter Engineer *
716 StrPn_akt Current value of lockout phase Engineer *
717 StrDia_akt Current value internal diagnostic code Engineer *
* Read only
With the ACS420, the lockout position storage is accessed via a specific menu.
PH_TNB 0
PH_TLO 1
PH_TNN 2
PH_STANDBY 3
PH_STARTVER 4
PH_THL1_1 5
PH_THL1_2 6
PH_TV 7
PH_TBRE 8
PH_TW1 9
PH_TW2 10
PH_TVZ 11
PH_TSA1_1 12
PH_TSA1_2 13
PH_TSA2_1 14
PH_TSA2_2 15
PH_TI 16
PH_MODULATION 17
PH_THL2_1 18
PH_THL2_2 19
PH_TN_1 20
PH_TN_2 21
PH_STOER 22
For meaning of the phase numbers, refer to the → Sequence diagrams
Phase designations /
numbers
Note