140/171
Siemens Building Technologies Basic Documentation LMU54... / LMU64... CC1P7494en
HVAC Products 12 Parameter list / legend of parameter bit fields LMU... 07.11.2002
No Name Group Function Range
No
QAA73
AGU2.310
Level
QAA73
AGU2.310
LevelNo
PC_Tool
Level
PC_Tool
Production data and version
289 KundeNr INFO values Official L & S customer number 0 ... 255 1
L&S service
5 ParaVersNr INFO values Parameter set version number 0 ... 65535 1
L&S service
(Development)
6 ParaSatzNr INFO values Parameter set number 0 ... 65535 1
L&S service
527 P_Kenn Parameterization
Identification of parameter set. PC tool programmed
from OEM level only when this parameter is identical
0 ... 255 2 L&S temp
7 FabJahr INFO values Production year 0 ... 255 0 L&S production
8 FabMonat INFO values Production month 0 ... 255 0 L&S production
10 FabNr INFO values Production number 0 ... 2147483647 0 L&S production
11 Pruefer INFO values Inspector code 0 ... 255 0 L&S production
Operating data, learn adaption range
68 BetrStd INFO values Hours run burner 0 ... 131070 hrs 718 Engineer* 1
L&S service
69 BetrStdHz INFO values Hours run heating mode 0 ... 131070 hrs 719 Engineer* 1
L&S service
70 BetrStdBw INFO values Hours run DHW heating 0 ... 131070 hrs 720 Engineer* 1
L&S service
71 BetrStdZone INFO values Hours run zone 0 ... 131070 hrs 721 Engineer* 1
L&S service
72 InbetrSetz INFO values Start counter 0 ... 327675 722 Engineer* 1
L&S service
246 TvSollMmiEeprom INFO values Initialization value of boiler setpoint potentiometer 20 ... 90 °C 1
L&S service
511 TvSollRedMmiEeprom Initialization
Initialization value of boiler setpoint potentiometer
5 ... 90 °C 1
L&S service
247 TrSollMmiEeprom INFO values Initialization value of room setpoint potentiometer 10 ... 30 °C 1
L&S service
512 TrSollRedMmiEeprom Initialization
Initialization value of room setpoint potentiometer
10 ... 30 °C 1
L&S service
248 TbwSollMmiEeprom INFO values Initialization value of DHW setpoint potentiometer 10 ... 80 °C 1
L&S service
513 TbwSollRedMmiEeprom Initialization Initialization of DHW setpoint potentiometer reduced 10 ... 80 °C 1
L&S service
74 MmiStatus HMI Selection of summer / winter operating modes 0 ... 255 724 Engineer* 1
L&S service
474 SwVersion_LMU INFO values
SW version of LMU for presentation on the OT
- 725 Engineer* - -
Measured value of ionization current
* Read only
Mixing valve clip-in
P-band of heating circuit 2 controller
166 TnHz2 Heating mode AGU2.500 Integral action time of heating circuit 2 controller 10 ... 873 s 574 OEM 4 OEM service
442 ZeitAufZu Heating mode AGU2.500
Running time of actuator in heating circuit 2
(TimeOpening / TimeClosing)
30 ... 873 s 596 Engineer 4 OEM service
443 SdHz2 Heating mode AGU2.500
Switching differential of 3-position controller in heating
circuit 2 (<= neutral zone (2K))
0 ... 2 K 4 OEM service
445 KoeffSperr Heating mode AGU2.500 Weighting factor for locking signal in heating circuit 2 0 ... 200 % 1
L&S service
LPB clip-in
17 LPBKonfig0 Boiler OCI420
Setting flags for time synchronization and power supply
0 ... 255 604 Engineer 5 Installer
LPB segment number of LMU
381 LPBAdrGerNr Boiler OCI420 LPB device number of LMU 0 ... 16 605 Engineer 5 Installer
416 LPBGeraeteVariante Boiler OCI420 Device variant within the LMU6x family 0 ... 255 1
L&S service
415 LPBErrorGerAlarm Boiler OCI420 Setting flags for configuring the device alarm on LPB 0 ... 255 1
L&S service
Burner control identification
Operating data
MCI
LPB