Siemens Building Technologies Basic Documentation LMU54... / LMU64... CC1P7494en
HVAC Products 12 Parameter list / legend of parameter bit fields LMU... 07.11.2002
KonfigRg5 Setting flags
H2Oueb Water shortage switch (input X11-3)
XXXX XX00 flow switch -> lockout
XXXX XX01 flow switch -> start prevention
XXXX XX10 pressure switch -> lockout
XXXX XX11 pressure switch -> start prevention
DrehBegr Speed limitation
XXXX X0XX OFF
XXXX X1XX ON
H2OUebSens Water pressure supervision with pressure sensor
XXX0 0XXX deactivated
XXX0 1XXX activated with start prevention
XXX1 0XXX activated with lockout
AbgasUeb Flue gas temperature supervision
X00X XXXX deactivated
X01X XXXX activated with start prevention
X10X XXXX activated with lockout
H2OUmlauf Water flow supervision with pressure sensor
0XXX XXXX error leads to start prevention
1XXX XXXX error leads to a lockout position
KonfigRg6 Setting flags
PIDinit
XXXX XXX0 internal
KundenRU Locking RU of other manufacture
XXXX XX0X OFF
XXXX XX1X ON
BwSoll Source of DHW setpoint
XXXX X0XX RU (if connected)
XXXX X1XX MMI (also when a RU is connected)
Sperrsignal Calculation of locking signal
XXXX 0XXX calculation of locking signal deactivated
XXXX 1XXX calculation of locking signal active
ReglStopSave Output can be stored at end of controller stop function
XXX0 XXXX output cannot be stored
XXX1 XXXX output can be stored
DrehGrWechsel Activation of fast speed limit changes
XX0X XXXX normal handling
XX1X XXXX accelerated handling of fast changes
KonfigRg7 Setting flags
ModQ1 Heating circuit pump
XXXX XXX0 multispeed
XXXX XXX1 modulating
DtBegr dt limitation
XXXX XX0X OFF
XXXX XX1X ON
DtRegelung dt control
XXXX X0XX OFF
XXXX X1XX ON