146/171
Siemens Building Technologies Basic Documentation LMU54... / LMU64... CC1P7494en
HVAC Products 12 Parameter list / legend of parameter bit fields LMU... 07.11.2002
FaEinstellFlags2 Setting flags of burner control section external components2
LPKon Function of free contact input (APS)
XXXX X000 not permitted
XXXX X001 input s ignal as a programmable input
XXXX X010 APS configuration2 (sequence diagram)
XXXX X011 APS configuration3 (sequence diagram)
XXXX X100 APS configuration4 (sequence diagram)
XXXX X101 contact open -> start prevention
GPKon Function of contact input GP
XXXX 0XXX no GP connected
XXXX 1XXX GP open -> start prevention
NLKon Level of postpurging
XXX0 XXXX prepurge level
XXX1 XXXX after the last operation control command
N_NachstellKon1 Speed readjustment on startup
XX0X XXXX OFF
XX1X XXXX ON
N_NachstellKon2 Speed readjustment on shutdown
X0XX XXXX OFF
X1XX XXXX ON
N_Nachstell_lern Learning function with speed readjustment
0XXX XXXX OFF
1XXX XXXX ON
FaEinstellFlags3 Setting flags of burner control section
Gebl_QAA Release or use of fan parameters of QAA73...
XXXX XXX0 no use of QAA fan parameters
XXXX XXX1 use of QAA fan parameters
Gebl_Impulse Number of pulses of fan’s Hall feedback signal per
revolution
XXXX X00X 2 pulses per revolution
XXXX X01X 3 pulses per revolution
XXXX X10X 4 pulses per revolution
CheckAnzAusg Number of outputs on clip-in function module for adaption
to current balance
XXXX 1XXX internally
TB_Konfig Flags for configuring the TL functions
TW_EIN TW ON / OFF
XXXX XXX0 TW OFF
XXXX XXX1 TW ON
Gradient_EIN Test exceeding temperature gradient ON / OFF
XXXX XX0X test exceeding temperature gradient OFF
XXXX XX1X test exceeding temperature gradient ON
DeltaT_1_EIN Checking excessive dT (> dTkTrSTB) ON / OFF
XXXX X0XX checking OFF
XXXX X1XX checking ON
DeltaT_2_EIN Checking excessive dT (> dTkTrSTB + 8K) ON / OFF
XXXX 0XXX checking OFF
XXXX 1XXX checking ON