121/219
Building Technologies Basic Documentation LMV27... CC1P7541en
21 Operating via AZL2 unit 17.12.2018
21.4.2 Manual control (manual request for output)
P
Vh
mi n
s%
Bild 4/0707
Burner is in operation.
The display shows oP: on the left, the
percentage of the current output on the right.
Example: oP: 20.0
F
1 s
P
Vh
mi n
s%
Bild 5/0707
Press
F
for 1 s.
The display shows LoAd:, the current output
flashes.
F
and
or
P
Vh
mi n
s%
Bild 6/0707
Press
or to adjust the required
manual output.
Example: oP: 23.0
P
Vh
mi n
s%
Bild 7/0707
Release
F
.
The current manual output flashes, indicating
that manual control is activated.
ESC
P
Vh
mi n
s%
Bild 8/0707
Press
ESC
for 3 s to return to automatic
mode.
The output no longer flashes.
The display shows oP: on the left, the
percentage value on the right.
Example: oP: 23.0