26 Parameter level 17.12.2018
26.11.11 Warm settings for «Lo 2 stage» and « Lo 3 stage»
P
Vh
mi n
s%
Bild 113/0707
Identification of start for setting the curve
parameters.
reset
Provided the load controller is
enabled!
P
Vh
mi n
s%
Bild 114/0707
Phase Standby (stationary)
P
Vh
mi n
s%
Bild 10/0707
Phase Fan ramp up
(fan motor = ON, safety
valve = ON)
P
Vh
mi n
s%
Bild 115/0707
Phase Traveling to prepurge position
P
Vh
mi n
s%
Bild 116/0707
Phase Prepurging
P
Vh
mi n
s%
Bild 117/0707
Phase Traveling to ignition position
Wait until the burner is operation and symbol
or is no longer highlighted!
The startup sequence stops in Phase 36 Traveling to ignition position.
The ignition position can be adjusted under cold conditions.
A
and
or
P
Vh
mi n
s%
Bild 149/0707
Ignition position P0 can be set only when
symbol
or is no longer highlighted.
Keep
depressed.
Press
or to adjust the value.
When symbol
or is no longer highlighted,
the next curvepoint P1 can be selected with
.