185/219
Building Technologies Basic Documentation LMV27... CC1P7541en
27 Parameter list 17.12.2018
Par. Parameter
Number of
Type Edit Value range Increment Default Password level
no.
elements
Min. Max. setting Write Read
19 = G mod gas actuator only
20 = Gp1 mod gas actuator only
21 = Gp2 mod gas actuator only
22 = Lo mod oil actuator only
23 = Ho mod separate circulation control ¹)
24 = Ho 2-stage separate circulation control ¹)
25 = Ho mod. without circulation control ¹)
26 = Ho 2-stage without circulation control ¹)
27 = Ho 3-stage without circulation control ¹)
28 = G mod mech air actuator only ¹)
29 = Gp2 mod mech air actuator only ¹)
¹) Selected operating mode is not released for the LMV27:
With select: Error code 210 diagnostic code 0
205
Function
Load controller contacts staged
0 = standard
1 = stages interchanged
1 Std_u8 Edit 0 1 1 0 OEM OEM
208 Program stop
0 = deactivated
1 = prepurge position (phase 24)
2 = ignition position (phase 36)
3 = interval 1 (phase 44)
4 = interval 2 (phase 52)
1 Selection Edit 0 4 1 0 HF (GA) HF (GA)
210 Alarm in the event of start prevention
0 = deactivated
1 = activated
1 Selection Edit 0 1 1 0 HF HF
211 Fan ramp up time 1 Time Edit 2 s 60 s 0,2 s 2 s HF HF
212 Maximum time down to low-fire 1 Time Edit 0,2 s 10 min 0,2 s 45 s HF HF
213 Waiting time until home run 1 Time Edit 2 s 60 s 0,2 s 2 s OEM OEM
214 Maximum time start release 1 Time Edit 0,2 s 10 min 0,2 s 25 s OEM OEM
215 Repetition limit safety loop
1 = no repetition
2...15 = 1...14 number of repetitions
16 = constant repetition
Recharging time:
Every 24 hours
1 Std_u8 Edit 1 16 1 16 HF HF
217 Maximum waiting time for detection of detector or pressure 1 Time Edit 5 s 10 min 0,2 s 30 s OEM OEM