Building Technologies Basic Documentation LMV27... CC1P7541en
27 Parameter list 17.12.2018
Par. Parameter
Number of
Type Edit Value range Increment Default Password level
no.
elements
Min. Max. setting Write Read
Index 1 = air
942 Active load controller source
1 = output during curve settings
2 = manual output
3 = default output via building automation
4 = default output via analog input
5 = external load controller via contacts
1 Selection
Read only
0 255 1 0 --- HF
947 Result of contact sensing (bit-coded)
Bit 0.0 = 1: Pressure switch-min
Bit 0.1 = 2: Pressure switch-max
Bit 0.2 = 4: Pressure switch valve proving
Bit 0.3 = 8: Air pressure switch
Bit 0.4 = 16: Load controller OPEN
Bit 0.5 = 32: Load controller ON
Bit 0.6 = 64: Load controller CLOSE
Bit 0.7 = 128: Safety loop
Bit 1.0 = 1: Safety valve
Bit 1.1 = 2: Ignition
Bit 1.2 = 4: Fuel valve V1
Bit 1.3 = 8: Fuel valve V2
Bit 1.4 = 16: Fuel valve V3 / pilot valve
Bit 1.5 = 32: Reset
2 Std_u8
Read only
0 255 1 0 --- IS
For query
via
ACS410
948 Contact feedback network counter register 14 Std_u8 Read only 0 255 1 0 --- HF
950 Required relay state (bit-coded)
Bit 0 = 1: Alarm
Bit 1 = 2: Safety valve
Bit 2 = 4: Ignition
Bit 3 = 8: Fuel valve V1
Bit 4 = 16: Fuel valve V2
Bit 5 = 32: Fuel valve V3 / pilot valve
1 Std_u8
Read only
0 255 1 0 --- IS
For query
via
ACS410
951 Mains voltage (normalized)
AC 230 V: Voltage = value x 1.710
AC 120 V: Voltage = value x 0.866
1 Std_u8 Read only 0 V 255 V 1 V 0 V --- HF (GA)
954 Intensity of flame 1 Std_u8
Read only
0% 100% 1% 0% --- IS
960 Actual flow rate (m³/h, l/h, ft³/h, gal/h) 1 Std_u16
read only
0 6553,5 0,1 0 --- IS
961 Phase (state for external modules and display) 1 Std_u8
Read only
0 255 1 0 --- IS
For query
via