MD Power Meter Technical Specifications
Single Phase, Three Phase-Four Wire (WYE), Three Phase-Three Wire
(Delta)
80 to 346 Volts AC Line-to-Neutral, 600V Line-to-Line, CAT III
0 to 4,000+ Amps depending on CT. 0.525 Vac maximum
158% of CT rating to maintain accuracy
True RMS using high-speed digital signal processing (DSP)
From L1 Phase to L2 Phase. 80 to 346 Vac CAT III 50/60 Hz
90 mA maximum. Non-user replaceable 0.5 Amp internal fuse protection.
12 kHz for voltage or current
Volts, Amps, kW, kWh, kVA, kVAR, kVARh, kVAh, Power Factor (PF),
All parameters for each phase and for system total.
0.2% (<0.1% typical) ANSI, C12.20-2010 Class 0.2
0.01 Amp, 0.1 Volt, 0.01 watt, 0.01 VAR, 0.01 VA, 0.01 Power Factor
depending on scalar setting
Bi-color LEDs (red and green): 1 LED to indicate communication, 3 LEDs
for correct CT-to-phase installation. One Digital Channel indicator.
Open Collector, 5 mA maximum current, 30V maximum open voltage,
optically isolated
P1 FLN over RS-485 Network
4800 baud (fixed, no adjustment)
RS 485 Transceiver unit load
size