MD-P1 Point Map by Application Number with Point Map Comparison
Supported P1 Applications
1
Siemens Industry, Inc.
37
9/30/2019
125-201
P1
Point
Point
Type
Type
No.
P1 Name
Units
Default
Value
Detail
Slope
for P1
Apps
Intercept
for P1
Apps
MD-P1
Series**
Apps
2771-
2777
MD-P1
Series*
*
App
2779
DEM1000*
Apps 710-
716
DEM2000*
Apps 717-
723
Power
67
LAI
3
KVA DEM MAX
kVA
0
System Maximum Instantaneous
Apparent Power Demand
= maximum demand value read
since startup or reset of demand
register
0.1
0
68
LAI
3
KVA DEM NOW
kVA
0
System Average Apparent Power
Demand
returns new value every minute, will
compare and post to min/max
registers
0.1
0
69
LAO
4
DATA SCALAR
3
A Value of 0-6 that changes the
scaling of certain registers.
1
0
70
LAO
4
DEMAND WIN
min
15
Demand window size in minutes;
default is 15 minutes.
1
0
71
LAO
4
VOLT MULT
1
Multiply volts values by this scalar.
Use with Step-down Transformer.
Affects all parameters that use volts
(such as, kW).
1
0
72
LDO
2
CTA TYPE
1
Select 1 = mV CT (on text = "MV")
or 2 = Rogowski CT (off text =
"ROGO")
1
0
73
LDO
2
CTB TYPE
1
Select 1 = mV CT (on text = "MV")
or 2 = Rogowski CT (off text =
"ROGO")
1
0
74
LDO
2
CTC TYPE
1
Select 1 = mV CT (on text = "MV")
or 2 = Rogowski CT (off text =
"ROGO")
1
0
75
LAO
4
CTA VALUE
A
100
Fractional part of NV_CT1
1
0
76
LAO
4
CTB VALUE
A
100
Fractional part of NV_CT2
1
0
77
LAO
4
CTC VALUE
A
100
Fractional part of NV_CT3
1
0