MD-P1 Point Map by Application Number with Point Map Comparison
Supported P1 Applications
1
Siemens Industry, Inc.
39
9/30/2019
125-201
P1
Point
Point
Type
Type
No.
P1 Name
Units
Default
Value
Detail
Slope
for P1
Apps
Intercept
for P1
Apps
MD-P1
Series**
Apps
2771-
2777
MD-P1
Series*
*
App
2779
DEM1000*
Apps 710-
716
DEM2000*
Apps 717-
723
"DELTA")
91
LAO
4
FREQ SET
Hz
60
Line frequency setting for metering:
50 = 50 Hz, 60 = 60 Hz, 400 = 400
Hz
1
0
92
LAO
4
SNAP MV
per
0.04
The amperage (current) value as a
percentage of the CT value that will
"snap" to 0 amps when the
amperage is < (snap % * CT Value)
0.01
0
93
LAO
4
SNAP RO
per
0.17
Similar to the SNAP mV percentage
above, this is used for Rogowski
coils (by default it is .17%)
0.01
0
94
LAO
4
SNAP VOLT
V
10
Defined in volts, not a percentage of
the maximum voltage input.
1
0
95
not used
not used
96
not used
not used
97
not used
not used
98
LDO
2
CLEAR ACUM
0
Resets all 'H' registers, accumulated
meter data (kWh, kWh, and so on)
stored in flash to CAM Default
value. (off text = "ACC", on text =
"CAM")
1
0
99
LAO
4
ERROR STATUS
0
1
0
* DEM P1 Applications 710 to 723
** MD-P1 Series P1 Applications 2772 to 2779