ECO REFERENCE MANUAL
13-16
Value Function of P051 to P055 and P356 Function,
low state
(0V)
Function,
high state
(>10V)
0 Input disabled - -
1 On right Off On right
4 OFF2 OFF2 On
5 OFF3 OFF3 On
6 Fixed frequencies 1-6 Off On
9 Start / Stop command selection from keypad
or digital terminals (for USS communication
operation P910 = 1 or 3)
Local Keypad
Start / Stop
Digital Terminal Start
/ Stop (or USS
communication
control)
10 Fault reset Off Reset on rising edge
11 Increase frequency* Off Increase
12 Decrease frequency* Off Decrease
13 Switch between analogue input frequency
setting and digital/keypad frequency setting
Analogue
setpoint
Keypad / Digital
setpoint
14 Disable the ability to change parameters ‘P’ enabled ‘P’ disabled
18 Fixed frequencies 1-6, but input high will also
request RUN when P007 = 0
Off On
19 External trip Off On
22 Download parameter set 0 from Ope*** Off Download
23 Download parameter set 1 from OPe*** Off Download
24 Switch analogue setpoint Analogue input
1 active
Analogue input 2
active
* Only effective when P007 = 0.
** Not available on P051, P052 or P356.
*** The motor must be stopped before downloading begins.
Downloading takes approx. 30 seconds.