DISPLAY MODE PARAMETERS
Parameter Function Range Default Units
Operating display
-
(output frequency) Hz
Displays the output selected by P001 (an Expert mode parameter).
Display selection via P001:
0 = Output frequency (Hz) 4 = Motor torque (% nominal)
1 = Frequency setpoint (i.e. speed at 5 = Motor speed (rpm)
which inverter is set to run) (Hz) 6 = USS serial bus status
2 = Motor current (A) 7 = PID Feedback signal (%)
3 = DC-link voltage (V) 8 = Output voltage (V)
The default setting (0) displays the inverter output frequency. If the inverter is in stand-by mode, the
flashing display will alternate between the setpoint frequency and actual output frequency, which will be
0 Hz when not being run.
In the event of a failure, the relevant fault code (Fnnn) is displayed.