ECO REFERENCE MANUAL
13-20
Parameter Function Range
[default]
Description / Notes
•
Pulse frequency 0 - 7
[rating
dependent]
[0]
Sets the pulse frequency (from 2 to 16 kHz)
and the PWM mode. If silent operation is not
absolutely necessary, the losses in the inverter
as well as the RFI emissions can be reduced
by selecting lower pulse frequencies.
0/1 = 16 kHz (230 V default)
2/3 = 8 kHz
4/5 = 4 kHz (400 V default)
6/7 = 2 kHz
Even numbers = normal modulation technique.
Odd numbers = lower loss modulation
technique used when operating mainly at
speeds above 5 Hz. (Not generally for fan
and pump applications)
Due to higher switching losses at increased frequencies, certain inverters may have their maximum
continuous current (100%) derated if the switching frequency is changed from the default value.
Model % of full load de-rating
16 kHz 8 kHz
MICROMASTER Eco
ECO1-75/3 100 100
ECO1-110/3 100 100
ECO1-150/3 100 100
ECO1-220/3 100 100
ECO1-300/3 100 100
ECO1-400/3 100 100
ECO1-550/3 100 100
ECO1-750/3 100 100
Model % of full load de-rating
16 kHz 8 kHz 4 kHz
MIDIMASTER Eco
ECO1-550/2 60 90 100
ECO1-750/2 55 90 100
ECO1-1100/2 64 90 100
ECO1-1500/2 60 100 100
ECO1-1850/2 47 80 100
ECO1-2200/2 43 79 100
ECO1-1100/3 57 90 100
ECO1-1500/3 50 83 100
ECO1-1850/3 64 90 100
ECO1-2200/3 55 75 100
ECO1-3000/3 50 90 100
ECO1-3700/3 47 88 100
ECO1-4500/3 40 75 100
ECO1-750/4 75 100 100
ECO1-1100/4 55 100 100
ECO1-1500/4 39 75 100
ECO1-1850/4 64 90 100
ECO1-2200/4 55 75 100