ECO REFERENCE MANUAL
13-24
Parameter Function Range
[default]
Description / Notes
Serial line time-out
(seconds)
0 - 240
[0]
This is the maximum permissible period
between two incoming data telegrams. This
feature is used to turn off the inverter in the
event of a communications failure.
Timing starts after a valid data telegram has
been received and if a further data telegram
is not received within the specified time
period, the inverter will trip and display fault
code F008.
Setting the value to zero switches off the
control.
Serial link nominal system
setpoint (Hz)
0 - 150.0
[50.0]
(60)North
America
Setpoints are transmitted to the inverter via
the serial link as percentages. The value
entered in this parameter represents 100%
(HSW = 4000H).
USS compatibility 0 - 2
[0]
0 = Compatible with 0.1 Hz resolution
1 = Enable 0.01 Hz resolution
2 = HSW is not scaled but represents the
actual frequency value to a resolution of
0.01 Hz (e.g. 5000 = 50 Hz).
Operation for Europe or
North America
Factory Default
0 for 230V Eco
2 for 380V to 500V Eco
2 for 525V to 575V Eco
0 - 2
[0 or 2]
This sets the inverter for European or North
America supply and nominal rating plate
frequency for the motor to:
0 = Europe (50 Hz and power ratings to kW)
1 = North America NEMA (60 Hz and
power ratings to hp)
2 = Automatic Selection based on mains
voltage
mains voltage <450V goes to 0
mains voltage >450V goes to 1
After setting P101 = 0 or 1 the inverter must
be re-set to factory defaults, i.e. P944 = 1 to
automatically set P013 = 60Hz, P081 =
60Hz, P082 = 1680rpm and P085 will be
displayed in hp.
After setting P101 = 2 the inverter will
automatically re-set to factory defaults, i.e.
P944 = 1
Inverter power rating
(kW/hp)
1.1 - 90.0
[

]
Read-only parameter that indicates the
variable torque power rating of the inverter
in kW. E.g. 7.5=7.5kW
If P101 = 1 then the rating is displayed in hp.