ECO REFERENCE MANUAL
15-29
Maximum Cable Length (m)
for MICROMASTER Eco & MIDIMASTER Eco
Inverter
Rating
(kW)
Standard (no output
reactor fitted)
Output Reactor
Fitted
Output Reactor
Fitted
Screened
Cable
Unscreened
Cable
Screened Cable Unscreened Cable
One
Reactor
Fitted
Two Reactors
Fitted in
Series
One
Reactor
Fitted
Two
Reactors
Fitted in
Series
110 200 300 300 400 400 500
132 200 300 300 400 400 500
160 200 300 300 400 400 500
200 200 300 300 400 400 500
250 200 300 350 450 400 550
315 300 300 350 450 400 550
*It is often a simpler and more economic connection solution to select an Eco inverter rating
which is one kW rating larger rather than to fit an output reactor, see section 14 for de-rating
information.
The maximum switching frequency must be limited to 2kHz for iron cored reactors and 4Hz for
ferrite cored reactors.
For multi-motor connection to a single inverter the total motor cable length is the sum of the
individual motor cable lengths.