ECO REFERENCE MANUAL
12-5
EMC
Class 3: Filtered - for residential, commercial and light industry
This level of performance will allow the manufacturer / assembler to self-certify compliance of their
apparatus with the EMC directive for the residential, commercial and light industrial environment as
regards the EMC performance characteristics of the power drive system. Performance limits are as
specified in the generic emission and immunity standards EN 50081-1 and EN 50082-1.
EMC Phenomenon Standard Level
Emissions:
Radiated Emissions EN 55022 Level B1
Conducted Emissions EN 55022 Level B1
Immunity:
Electrostatic Discharge EN 61000-4-2 8 kV air discharge
Burst Interference EN 61000-4-4 1 kV power cables, 0.5 kV control
The MICROMASTER Eco and MIDIMASTER Eco units are intended exclusively for
professional applications. Therefore, they do not fall within the scope of the harmonics
emissions specification EN 61000-3-2.