3. If used, set appropriate I2C addresses for I/O modules:
– Input modules (DF8040) have addresses 1 or 2
– Output module (DF8020) has address 1
– Power supply supervision module (DF8090), factory set to address 8.
4. Connect and install the modules, then connect the I/O points to the modules.
For more information about the DF8000 Input/Output modules, including
installation details, see documents:
DF8000 Datasheet
(document no. A6V10081184)
DF 8000 ICC
(document no A6V10081388)
5. Connect power supply.
See Figure
Power connections
if using a DF8090 power supply supervision
module.
Note: Connectors in Figure
NK822x electrical interfaces (top view)
are valid for
NK8222, NK8223 and NK8225.