9
Maintenance and diagnostics
Correcting communication failures
82
Building Technologies
A6V10062437_a_en
CPS Fire Safety
30.01.2019
Note: If these settings are incorrect, you will have no communication in runtime,
though no error message will be generated.
9.5.5 No fault generated by network failure - MP3.15 and higher
If you do not receive a fault from an NK8000 when a network failure has occurred,
or if there is a long delay before you receive the fault, decrease the Timer for Micro
Interruptions Threshold communication parameter.
Note: Default value is 0 sec.