Fail-Safe Modules   
7.5 4/8 F-DI DC24V PROFIsafe Digital Electronic Module 
  ET 200S Distributed I/O System - Fail-Safe Modules 
112  Installation and Operating Manual, 08/2008, A5E00103686-07 
Reintegration After Discrepancy Error Parameter 
With this parameter you can define the criteria for clearing discrepancy errors which, when 
fulfilled, facilitate reintegration of the relevant input channels. Programming options: 
●  "Zero signal test required" or 
●  "Zero signal test not required" 
Requirements 
Parameter settings: 
●  Sensor evaluation: "1oo2 evaluation" 
"Zero signal test required" 
When "Zero signal test required" is set, a discrepancy error is not considered cleared until a 
zero signal is set at both input channels. 
When using nonequivalent sensors, that is, "2-channel nonequivalent" is set at the "Type of 
sensor interconnection" parameter, the zero signal must again be set at the channel which 
provides the wanted signal. 
"Zero signal test not required" 
When "Zero signal test not required" is set, a discrepancy error is considered cleared when a 
discrepancy no longer exists between the two input channels.  
SIMATIC S7 F-modules, for which you cannot program the "Reintegration after discrepancy 
error" parameter, also behave in this way.