General Technical Specifications   
6.6 Specifications for Nominal Line Voltages, Isolation Tests, Protection Class, and Type of Protection 
  ET 200S Distributed I/O System - Fail-Safe Modules 
60  Installation and Operating Manual, 08/2008, A5E00103686-07 
6.6  Specifications for Nominal Line Voltages, Isolation Tests, Protection 
Class, and Type of Protection 
Rated Voltages for Operation 
The fail-safe signal modules operate at a rated voltage of 24 VDC. The tolerance range is = 
20.4 VDC to 28.8 VDC. 
Test Voltages 
Refer to the technical specifications of the fail-safe modules for information regarding the test 
voltages. 
Protection Class 
Protection class I in accordance with IEC 60536 (VDE 0106, Part 1), i.e. ground terminal 
required on DIN rail! 
Type of Protection 
Type of protection IP20 to EN 60529 for all F-modules, that is: 
●  Protection from contact with standard probes 
●  Protection from foreign bodies larger than 12.5 mm in diameter 
●  No special protection against water 
See also 
Safe Functional Extra Low Voltage for Fail-Safe Modules (Page 33)