Fail-Safe Modules 
  7.6 EM 4 F-DI/3 F-DO DC24V PROFIsafe digital electronic module 
ET 200S Distributed I/O System - Fail-Safe Modules 
Installation and Operating Manual, 08/2008, A5E00103686-07 
153 
Wiring Diagram for Nonequivalent Connection of Two Single-Channel Sensors to Two Channels 
Two single-channel sensors are connected via two channels to two inputs of the F-module 
for each process signal (1oo2 evaluation).  
The left-hand channels on the F-module (DI0 through DI3) supply the wanted signals. If no 
faults are detected, these signals will be available in the I/O area for inputs on the F-CPU. 
The sensors can also be connected to an external sensor supply. 
30(
)',)'2
/ 0
/ 0
96 ',
6
6
6
6
', ', ', ', ', ', ',
7KHOHIWKDQGFKDQQHOVRQWKH)PRGXOHVXSSO\WKHZDQWHGVLJQDOV
 
Figure 7-44  Wiring diagram EM 4 F-DI/3 F-DO DC24V - two 1-channel sensors connected via two 
channels, internal sensor supply 
 
WARNING 
 
To achieve SIL3/Category 3/PLd using this wiring, you must use a suitably qualified sensor.
 
Assignable Parameters for Application 1.3  
You can activate or deactivate the "short-circuit test" parameter. For digital inputs connected 
to an external supply, set the "Sensor supply" parameter for the corresponding digital input 
to "external". The program will otherwise report a "short circuit" diagnostics event if the 
"short-circuit test" is activated.