Siemens Standard application AHU CE1P3977en_02
Building Technologies Communication 01.02.2010
Parameter Range Function
Min send intervall Displays current minimum interval for sending
values. A value may only be sent a maximum of
one time during this interval.
Settings Go to settings page to parameterize LON bus.
Main Index > System overview > Communication > LON > LON settings
Parameter Range Function
Send heart beat 0…65535 [s] Set interval for sending values.
Receive heart beat 0…65535 [s] Set interval for receiving values.
Min send interval 0…65535 [s] Set minimum interval for sending values.
9.3.2 Commission external LON module
Participating devices
Climatix POL 636 controller.
LON module POL906.
Prerequisites for commissioning a LON section:
The SAPRO application is fully commissioned.
Level 4 (password 2000).
Mapping file (OBH.bin) is loaded.
LON bus parameteriza-
tion
Devices
Prerequisites
Basis Document Siemens Climatix Control System
BDCX.100820.01GB
Page 125