Siemens Standard application AHU CE1P3977en_02
Building Technologies Alarming 01.02.2010
19.5 Alarm list / history settings
Parameter Range Function
Alarm list
Reset.
Reset / acknowledge pending alarms.
Sort order 1
Time
Name
AlarmClass
State
Main sorting criteria
Sort by data and time.
Sort alphabetically in ascending order.
Sort by notification class (0,1,2,3 corresponding
to Danger/High/Low/Warning).
Sort by status (fault, no fault).
Sort order 2 Time
Name
AlarmClass
State
Auxiliary sort criteria:
See Sort order 1.
Descending order
Passive
Active
Alarms sorted in ascending or descending order.
What is the criteria applied for?
Ascending.
Descending.
Alarm history
Reset. Deletes history list.
Sort order 1 Time
Name
AlarmClass
State
Main sorting criteria
See Alarm list.
Sort order 2 Time
Name
AlarmClass
State
Auxiliary sort criteria:
See Alarm list.
Descending order Passive
Active
See Alarm list.
Parameter
Basis Document Siemens Climatix Control System
BDCX.100820.01GB