Siemens Standard application AHU CE1P3977en_02
Building Technologies Communication 01.02.2010
Description lang English
Swedish
German
Lang4
Lang5
Description language for the EDE file on BACnet
integration.
Security level 0...9 Access level via BACnet.
Alarm server ID 0…8
Alarm device ID1
Alarm device ID2
Alarm device ID3
Comm mapping 16384 Mapping table for communication:
(16384 = Mapping table com1 is used).
(16385 = Mapping table com2 is used, but not
implemented).
Do not change this value!
Reset required !!
Execute
(Display only) As a matter of principle, the con-
troller must be set after parameterization to as-
sume the data (on the "Comm module overview"
page).
Main Index > System overview > Communication > Comm module overview >
Module[x] BACnet IP > TCP/IP settings
Parameter Range Function
DHCP
Active
Passive
Displays type of address assignment:
DHCP server issues addresses.
IP address is fixed.
WINS name Enter name of DHCP servers.
IP Enter IP address for DHCP=Passive.
Mask Enter subnet mask.
Gateway Enter gateway address.
Write settings Passive
Active
Assume changed data on the module.
Reset required !!
Execute
(Display only) As a matter of principle, the con-
troller must be set after parameterization to as-
sume the data (on the "Comm module overview"
page).
TCP/IP parameteriza-
tion
Basis Document Siemens Climatix Control System
BDCX.100820.01GB
Page 130

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens POL638 Series and is the answer not in the manual?

Siemens POL638 Series Specifications

General IconGeneral
BrandSiemens
ModelPOL638 Series
CategoryControl Systems
LanguageEnglish

Related product manuals