137 / 244
Siemens Standard application AHU CE1P3977en_02
Building Technologies Save / restore parameters 01.02.2010
Reset required !!
Execute
Resets after downloading parameters.
Passive position.
Reset. The controller operate using the con-
figuration loaded from the SD card.
Par service load
Execute
Requires access level 6.
Downloads parameter files from commissioning.
Passive position.
Download. The display than returns to ser-
vice load.
Par factory load
Execute
Requires access level 4.
Downloads parameter files from factory.
Passive position.
Download. Display returns to .
Par service save
Execute
Requires access level 4.
Saves parameter files from the commissioning to
the controller.
Passive position.
Save. Display returns to .
Par factory save
Execute
Requires access level 2.
Saves parameter files from factory.
Passive position.
Save. Display returns to .
Application default
Execute
Requires access level 2.
Download configuration with all parameters per
the overall standard program loaded at the fac-
tory. Requires complete re-commissioning!
Passive position.
Download. Display returns to .