Siemens Standard application AHU CE1P3977en_02
Building Technologies System settings 01.02.2010
Parameter Range Function
0
1
2
3
4
5
6
7
8
9
10
Fifth to last week.
Fourth to last week.
Third to last week.
Second to last week.
Last week.
Not allowed.
First week.
Second week.
Third week.
Fourth week.
Fifth week.
Start hour 0...23 [h] Time of day of change to daylight saving time.
Start delay -32768...32767 [h] Delay for changeover.
End month Jan…Dec Month for changeover to standard time.
End week day Mo…Su Day of the week for changeover to standard
time.
End offset
0
1
2
3
4
5
6
7
8
9
10
Week of the month for the changeover to stan-
dard time:
Fifth to last week.
Fourth to last week.
Third to last week.
Second to last week.
Last week.
Not allowed.
First week.
Second week.
Third week.
Fourth week.
Fifth week.
End hour 1...23 [h] Time of day for changeover to standard time.
End delay -32768...32767 [h] Missing
UTC-difference -720...720 [min] Difference between local time and global UTC.
The following generally applies: UTC - Local time
= UTC-difference. For MET (Default): 12:00 -
13:00 = - 60 min.
Caution: Daylight saving time not considered!
Basis Document Siemens Climatix Control System
BDCX.100820.01GB
Page 144