Siemens Standard application AHU CE1P3977en_02
Building Technologies System settings 01.02.2010
Diagnoses ram, objects and COV or alarm handler clients.
Parameters can be read with level 4. They are always write-protected.
Main Index > System overview > All system settings > Diag object handler
Parameter Range Function
Actual objects Number of actual objects for the enabled configuration.
Act object moemory ... [B] Actual required memory.
Act int memory ... [B] Maximum amount of available dynamic memory.
COV act clients Number of subscribed internal and external COV clients.
ALH act clients Number of subscribed internal and external alarm handler
clients.
Valid objects Yes
No
Displays whether valid data is present in the object han-
dler. For faults, evaluate the measuring and control task of
the diagnostic object.
Version Object handler version.
Data check sum Internal checksum of the enabled configuration.
Max objects Maximum number of enabled objects.
Max object memory ... [B] Maximum memory for objects.
Max int memory ... [B] Maximum memory for data.
COV max clients Maximum number of internal and external COV clients.
ALH max clients Maximum number of internal and external alarm handler
clients.
Parameter
Basis Document Siemens Climatix Control System
BDCX.100820.01GB