Siemens Standard application AHU CE1P3977en_02
Building Technologies Functions 01.02.2010
Parameter Range Function
External control
Auto
Off
Stage 1
Stage 2
Stage 3
Displays current plant command from hardware
plant switch.
Auto mode: Time switch catalog, night cooling,
etc., can switch on the plant.
Plant off.
Plant operating in stage 1 (using setpoint stage 1
for analog controlled plants).
Plant operating in stage 2 (using setpoint stage 2
for analog controlled plants).
Plant operating in stage 3 (using setpoint stage 3
for analog controlled plants).
Roomunit op mode
Auto
Comfort
Standby
Economy.
Displays present plant command from room unit
Auto mode: Time switch catalog, night cooling,
etc., can switch on the plant.
Plant operating in Comfort Mode.
Plant is in standby.
Plant operating in Economy Mode.
Night kick exh tmp
--- Starts plant to update sensor values for return-air
controlled plant and activated night cooling or Unit-
Start TmpDelta.
(Temperature difference start). Jumps to page to
parameterize night kick.
Night cooling
--- Night cooling (free cooling). Jumps to page to pa-
rameterize night cooling.
Tmp start
--- Starts plant at night based on temperature differ-
ence. Jumps to page to parameterize temperature
difference start.
Boost
--- Boost plant start. Jumps to page to parameterize
boost plant start.
Power up delay
0…36000 [s] Delayed plant start after controller restart.
Basis Document Siemens Climatix Control System
BDCX.100820.01GB
Page 37